About this good practice
FERC Order No. 881 (December 2021) requires US public utility transmission providers to replace static, conservative line ratings with ambient-adjusted ratings (AARs) for near-term transmission service, defined as service that ends no more than 10 days after the request date. AARs must be recalculated at least hourly using an up-to-date ambient-temperature forecast, accounting for the absence of solar heating at night. Because actual temperatures are usually lower than the worst-case values assumed in static ratings, AARs often release transfer capability that fixed ratings hide, reducing congestion costs. They also guard against overestimating capacity on unusually hot days. Beyond the 10-day horizon, providers use seasonal ratings covering at least four seasons, updated annually.
The rule applies to all transmission lines, with exceptions where capability is not affected by temperature or solar heating. Transmission owners must share ratings and methodologies with their providers and market monitors, and providers must keep a database of ratings and methodologies. Dynamic line ratings are not mandated, but implementing them satisfies the AAR requirement, and system operators (RTOs) must be able to accept them.
Providers had to submit revised transmission service rules within 120 days of the order’s effective date and fully implement the changes within three years of that deadline, setting the original implementation deadline at 12 July 2025. Subsequent extensions have delayed compliance in some regions, with deadlines ranging from April 2026 (PJM) to December 2028 (NYISO).
Read more about the good practice