About this measure
Require that distributed energy resources be registered, recording location, connection point, capacity, technology, ownership and controllable capability. A distribution system operator cannot manage, forecast or call on resources it cannot enumerate, and in many systems its record of what is connected behind the meter is incomplete, outdated or unusable operationally. A register is a low-cost entry point to distribution-level visibility, since it requires no field hardware, and it is the precondition for most of what follows: hosting capacity assessment, load and generation forecasting, fault analysis, flexibility procurement and aggregation all depend on knowing what exists and where. Registration should be tied to the connection process so that the record is created when an asset connects rather than reconstructed afterwards, with reporting obligations on installers or manufacturers where customers cannot reasonably supply technical detail. Data quality matters more than coverage in the early stages, and entries should be validated against metering and inspection data. Access should be governed so that operators, planners and, where appropriate, aggregators can use the register, subject to the privacy safeguards in recommendation 7.3.