Regulators should require system operators to establish real-time operational frameworks to maintain stability in systems with a high share of inverter-based resources. These frameworks should define how operators monitor and manage frequency stability, voltage stability, inertia, fault levels, oscillations, system strength, protection performance and control interactions under changing system conditions. Because these quantities vary continuously with the dispatch and cannot be assured by design margin alone, the framework should include look-ahead security assessment: continuous automated evaluation of whether the system would remain stable under credible contingencies given its current and forecast state, with defined thresholds and operator actions as limits are approached. The same real-time discipline should extend beyond narrowly defined stability to managing voltage under low-demand conditions and to restoration readiness as inverter-based resources become the plant available to restart the system. Ensure this is coordinated with the emergency preparedness established earlier in this recommendation and with the stability and restoration services defined and procured under recommendation 6.2. This depends on the validated dynamic models required earlier in this recommendation and on the capability requirements set under recommendation 4.1, since an assessment is only as reliable as the equipment models beneath it.